No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
P3-40
(0CEF)
Pre-Charge Lag Pump
Select
Precharge LagSel
0: Disabled
2: Pump2 (H2-0X=80)
3: Pump3 (H2-0X=81)
4: Pump4 (H2-0X=82)
5: Pump5 (H2-0X=83)
6: Pump6 (H2-0X=84)
Selects which of the lag pumps can come on during a pre-charge.
0: Disabled
2: Pump 2 (H2-0
o
= 80)
3: Pump 3 (H2-0
o
= 81)
4: Pump 4 (H2-0
o
= 82)
5: Pump 5 (H2-0
o
= 83)
6: Pump 6 (H2-0
o
= 84)
Default: 0
Range: 0; 2 to 6
–
P3-41
(0CF0)
Pre-Charge Lag Pump
Run Time
Precharge Lag Tm
Sets the length of time that the lag pump specified in P3-40 is
energized.
Default: 0.0 min
Min.: 0.0
Max.: 3600.0
–
P3-42
(0CF1)
Post-Pre-Charge Lag
Pump Operation
Post PreChg Lag
0: Turn Off
1: Continue
Determines whether the lag pump set in pre-charge (P3-40)
turns off or maintains its state when pre-charge is completed.
0: Turn off
1: Continue
Default: 0
Range: 0, 1
–
P3-43
(0CF2)
Pre-Charge Lag Pump
Delay Time
PreChg Lag Delay
Sets the length of time that the drive is in the pre-charge mode
before the lag pump set in P3-40 is energized.
Default: 2.0 min
Min.: 0.0
Max.: 600.0
–
P3-50
(0CF9) Pump 2 Frequency
Shutdown Level
P2 Shutdown Freq
Sets the level used for the multiplex pumping operation.
Parameter is active only when P3-02 is set to 0 or 2.
When P3-02 is set to 0 and a total of two pumps are running, the
last pump (Pump 2) that was brought online will be shut down
by opening the dedicated multi-function discrete output
(H2-0
o
= 80 to 84) when the output frequency falls below the
level set in this parameter for the time set in P3-09.
When P3-02 is set to 2 and a total of two pumps are running, the
last pump (Pump 2) that was brought online will be shut down
by opening the dedicated multi-function discrete output
(H2-0
o
= 80 to 84) when the delta feedback (setpoint minus
feedback) has exceeded the level programmed in this parameter
for the time set in P3-09.
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
P3-60
(11E5) Pump 3 Frequency
Shutdown Level
P3 Shutdown Freq
Sets the level used for the multiplex pumping operation.
Parameter is active only when P3-02 is set to 0 or 2.
Parameter function is similar to P3-50, except for Pump 3
instead of Pump 2.
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
P3-70
(11EF) Pump 4 Frequency
Shutdown Level
P4 Shutdown Freq
Sets the level used for the multiplex pumping operation.
Parameter is active only when P3-02 is set to 0 or 2.
Parameter function is similar to P3-50, except for Pump 4
instead of Pump 2.
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
P3-80
(11F9) Pump 5 Frequency
Shutdown Level
P5 Shutdown Freq
Sets the level used for the multiplex pumping operation.
Parameter is active only when P3-02 is set to 0 or 2.
Parameter function is similar to P3-50, except for Pump 5
instead of Pump 2.
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
–
P3-90
(1203)
Pump 6 Frequency
Shutdown Level
P6 Shutdown Freq
Sets the level used for the multiplex pumping operation.
Parameter is active only when P3-02 is set to 0 or 2.
Parameter function is similar to P3-50, except for Pump 6
instead of Pump 2.
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
–
<1> Unit is determined by P1-02, System Units, setting.
u
P4: Pump Advanced
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
P4-01
(0CFA) Pre-Charge Level
Pre-Charge Level
Runs the drive at the frequency set in P4-02.
The drive will stop when one of the following conditions occurs:
• The feedback level rises above the level set in P4-01
• The pre-charge time set in P4-03 expires
• The low water digital input is deactivated (#8F)
Min.: 0.0
Max.: 6000.0
P4-02
(0CFB) Pre-Charge Frequency Pre-Charge Freq.
Sets the frequency reference used when the Pre-Charge function
is active.
Default: 0.0 Hz
Min.: 0.0
Max.: [E1-04]
B.12 P: Pump Parameters
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
331