No.
Parameter Name
Setting Values
Q6-09
PI Auxiliary Control Low Level Detection
Default: 0.0
Range: 0.0 to 999.9
Q6-10
PI Auxiliary Control Low Level Detection Time
Default: 0.1 min
Range: 0.0 to 300.0 min
Q6-11
PI Auxiliary Control Low Level Detection Selection
Default: 1
Range: 0 to 3
Q6-12
PI Auxiliary Control High Level Detection
Default: 0.0
Range: 0.0 to 999.9
Q6-13
PI Auxiliary Control High Level Detection Time
Default: 0.1 min
Range: 0.0 to 300.0 min
Q6-14
PI Auxiliary Control High Level Detection Selection
Default: 1
Range: 0 to 3
Q6-15
PI Auxiliary Control Level Detection Restart Time
Default: 5.0 min
Range: 0.1 to 6000.0 min
Q6-16
PI Auxiliary Control P Gain
Default: 2.00
Range: 0.00 to 25.00
Q6-17
PI Auxiliary Control I Time
Default: 5.0 s
Range: 0.0 to 360.0 s
Q6-18
PI Auxiliary Control Detection Time Unit
Default: 0
Range: 0, 1
Q6-19
PI Auxiliary Control Feedback Wirebreak
Default: 2
Range: 0 to 2
Q6-20
PI Auxiliary Control Main PI Control
Default: 1
Range: 0, 1
Q6-21
PI Auxiliary Control Level Unit Selection
Default: 1
Range: 0 to 11; 26
Q6-22
PI Auxiliary Control Level Decimal Place Position
Default: 1
Range: 0 to 3
Q6-23
PI Auxiliary Control Output Level Selection
Default: 1
Range: 0, 1
Q6-24
PI Auxiliary Control Maximum Level
Default: 0.0
Range: 0.0 to 6000.0
Q6-25
PI Auxiliary Control Activation Level
Default: 0.0 PSI
Range: 0.0 to 6000.0
Q6-26
PI Auxiliary Control Activation/Deactivation Delay
Default: 2 s
Range: 0 to 3600 s
Q6-32
PI Aux Units Custom 1
st
Character
Default: 41
Range: 20 to 7A
Q6-33
PI Aux Units Custom 2
nd
Character
Default: 41
Range: 20 to 7A
Q6-34
PI Aux Units Custom 3
rd
Character
Default: 41
Range: 20 to 7A
U1-96
PI Auxiliary Control Feedback Level
–
H1 Multi-Function Digital Input Settings
H1-
oo
Function
Description
82
PI Switch to Aux
Closed: PI Auxiliary Control (Q6-
oo
) becomes the primary PI loop, disabling the System PI controller
(b5-
oo
). Overrides Q6-20 if set to 0 (Disable Effect on Speed Control).
H2 Multi-Function Digital Output Settings
H2-
oo
Function
Description
9E
Low PI Aux Lvl
Energizes when the PI Aux Feedback Level falls below the Low PI Aux Level (Q6-09), or if there is a
LOAUX – Low PI Aux Level Fault.
9F
Hi PI Aux Lvl
Energizes when the PI Aux Feedback Level rises above the High PI Aux Level (Q6-12), or if there is a
HIAUX – Hi PI Aux Lvl Fault.
4.6 U1000 iQpump Presets and Functions
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
135
4
Start-Up Programming & Operation