P4-11
Output
frequency
“Thruse Active”
Message &
Digital Output
(H2-0
☐
= A9)
Run
command
C1-01
(or selected)
Accel Rate
P4-12 Thrust Frequency
P4-13
Thrust Bearing
Ramp to Stop (b1-03 = 0)
C1-02
(or selected)
Decel Rate
Figure 4.37 Thrust Bearing
n
P4-17: Utility Start Delay
Sets the delay time after power up until the drive will recognize a Run command present within one second of power up or
when the Run command is jumpered on the terminal strip.
This is useful in preventing a peak power surge when multiple drives power up and begin accelerating simultaneously. This
function works when the drives all have different P4-17 settings to spread out the power draw during acceleration.
If the Run command is removed and reapplied during the P4-17 time, the drive will cancel the utility start delay and immediately
begin running.
The Utility Start Delay is applied when the drive is auto-restarting after an Undervoltage (Uv), Overvoltage (ov), Power Supply
Over Voltage (Aov), Power Supply Undervoltage (AUv) or a Power Supply Frequency Fault (Fdv) condition.
No.
Parameter Name
Setting Range
Default
P4-17
Utility Start Delay
0.0 to 1000.0 min
0.2 min
n
P4-40: Pressure Reached Detection Selection
Sets the drive state that must be met when triggering the Pressure Detection digital output.
No.
Parameter Name
Setting Range
Default
P4-40
Pressure Reached Detection Selection
0 to 2
0
Setting 0: Always
Triggers the digital output regardless of drive status (even when the drive is stopped or sleeping).
Setting 1: Drive Running
Triggers the digital output if the drive is producing output voltage (not baseblocked) to the motor. The digital output will not
engage when the drive is sleeping.
Setting 2: Run Command
Triggers the digital output when there is an active Run command.
n
P5-02: HAND Reference 1
Sets the frequency reference of HAND mode. When the drive is stopped, pressing the HAND key will start the drive and the
drive will accelerate to the P5-02 setting.
No.
Parameter Name
Setting Range
Default
P5-02
HAND Reference 1
0.0 to E1-04
40.0 Hz
n
P5-04: HAND Key Function Selection
Selects whether the HAND key on the HOA keypad is active. Disabling this function by setting P5-04 to 0 will prevent the
drive from entering HAND Mode.
No.
Parameter Name
Setting Range
Default
P5-04
HAND Key Function Selection
0, 1
1
4.7 Basic U1000 iQpump Setup and Application Preset Parameters
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
169
4
Start-Up Programming & Operation