u
Water Level / Suction Pressure Control
This function provides the ability to use the Low and High Level Detection feature of Water Level or Suction Pressure Control
without affecting the output speed (drive main PI control).
This function will affect the output speed only when setting Q4-01 > 0 to enable Water Level Control will and setting Q4-20
to 1 to enable Water Level Speed Control.
In all other cases, only Sleep at Minimum Water Level and Level Detection features are usable.
This function will affect the output speed only when setting Q5-01 > 0 to enable Suction Pressure Control will and setting
Q5-20 to 1 to enable Suction Pressure Speed Control.
In all other cases, only Sleep at Minimum Suction Pressure and Pressure Detection features are usable.
n
Related Parameters
No.
Parameter Name
Setting Values
Q4-20
Water Level Speed Control
Default: 1
Range: 0, 1
Q5-20
Suction Pressure Speed Control
Default: 1
Range: 0, 1
u
Delta Data Entry
Delta Data Entry allows the user to set the Low and High Feedback Detection Levels relative to the current setpoint and
establish a PI setpoint when PID is not active.
Parameter/Condition
Delta Entry
Absolute Entry
Range Display
(Toggles Automatically)
P1-04 Start Draw Down Level PID Direct-
acting
-0.0 to -999.9
0.0 to 999.9
(0.0 to 999.9) <– –> “–Sub frm SetPt”
P1-04 Start Draw Down Level PID Inverse-
acting
+0.0 to +999.9
0.0 to 999.9
(0.0 to 999.9) <– –> “+Add to SetPt”
P1-08 Low Feedback Level
-0.0 to -999.9
0.0 to 999.9
(0.0 to 999.9) <– –> “–Sub frm SetPt”
P1-11 High Feedback Level
+0.0 to +999.9
0.0 to 999.9
(0.0 to 999.9) <– –> “+Add to SetPt”
The following conditions will change the setpoint in order of priority when the drive is a non-PID mode or when PID is
disabled:
The default Setpoint is Q1-01 (Setpoint 1)
1.
Setpoints Q1-02 to Q1-04 when Multi-setpoint Digital Inputs are active (H1-
oo
= 8D, 8E, 83, 84, or 85)
2.
MEMOBUS Setpoint when MEMOBUS PID Setpoint enable bit is set
3.
Pulse Input RP when H6-01 = 2 (PID Setpoint)
4.
Analog Input when H3-
oo
= C (PID Setpoint).
n
Related Parameters
No.
Parameter Name
Setting Values
P1-04
Start / Draw Down Level
Default: 0.0
Range: 0.0 to 999.9
P1-08
Low Feedback Level
Default: 0.0
Range: 0.0 to 999.9
P1-11
High Feedback Level
Default: 155.0
Range: 0.0 to 999.9
4.6 U1000 iQpump Presets and Functions
114