No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
Q6-18
(0F61)
PI Auxiliary Control
Detection Time Unit
PI Aux Time Unit
0: Minutes (min)
1: Seconds (sec)
Sets the time unit for Q6-10 and Q6- 13.
0: Minutes (min)
1: Seconds (sec)
Default: 0
Range: 0, 1
–
Q6-19
(0F62)
PI Auxiliary Control
Feedback Wirebreak
PI Aux WireBreak
0: No Display
1: Alarm Only
2: Fault
Sets the behavior of the analog input selected for PI Aux
Feedback when it is programmed to receive a 4 to 20 mA signal
and the signal is lost.
0: Disabled
1: Alarm Only
2: Fault (no retry, coast to stop)
Default: 2
Range: 0 to 2
–
Q6-20
(0F63)
PI Auxiliary Control
Main PI Control
PI Aux Spd Cntrl
0: Disabled
1: Enabled
Selects whether the PI Auxiliary Controller has an effect on
output speed.
0: Disabled
1: Enabled
Default: 1
Range: 0, 1
–
Q6-21
(0F64)
PI Auxiliary Control
Level Unit Selection
PI Aux Lvl Unit
0: No Unit
1: PSI :lb/SqrInch
2: Pa:Pascals
3: Bar:Bar
4: "WC:InchOfWater
5: "Hg:Inch Mercury
6: ft: feet
7: m: meters
8:
°
F:DegFarenheit
9:
°
C:DegCelsius
10: %: Percent
11: kPA: kilopascal
26: Custom
(Q6-32~34)
Set the unit displayed for the PI Aux Level parameters and
monitor.
0: No unit
1: PSI: Pounds per square inch
2: Pa: Pascals
3: Bar: Bar
4: ”WC: Inch of water
5: ”Hg: Inch of Mercury
6: ft: feet
7: m: meters
8:
°
F: Degrees Fahrenheit
9:
°
C: Degrees Celsius
10: Percent
11: kPA: kilopascal
26: Custom (Q6-32 to Q6-34)
Default: 1
Range: 0 to 11;
26
–
Q6-22
(0F65)
PI Auxiliary Control
Level Decimal Place
Position
PI Aux LvlDecPt
0: No Dec (XXXXX)
1: 1 Dec (XXXX.X)
2: 2 Dec (XXX.XX)
3: 3 Dec (XX.XXX)
Sets the number of decimal places for the PI Aux Level
parameters and monitor.
0: No Dec (XXXXX)
1: 1 Dec (XXXX.X)
2: 2 Dec (XXX.XX)
3: 3 Dec (XX.XXX)
Default: 1
Range: 0 to 3
–
Q6-23
(0F66)
PI Auxiliary Control
Output Level Selection
PI Aux OutLvlSel
0: Direct Acting
1: Inverse Acting
Determines whether the PI Auxiliary Controller is Direct-acting
(feedback higher than setpoint results in lower speed) or
Inverse-acting (feedback lower than setpoint results in lower
speed).
0: Direct Acting
1: Inverse Acting
Default: 1
Range: 0, 1
Q6-24
(0F67) PI Auxiliary Control
Maximum Level
PI Aux Max Lvl
Sets the value above which the level must rise for longer than
the time set in Q6-05 for the drive to go to sleep and turn off all
lag pumps.
This feature is disabled when set to 0.
Min.: 0.0
Max.: 6000.0
–
Q6-25
(0F68)
PI Auxiliary Control
Activation Level
PI Aux Act Lvl
For Inverse Acting (Q6-23 = 1):
When the PI Aux Feedback drops below this level for more than
the Q6-26 time, PI Aux Control is activated allowing it to affect
the output frequency. When the PI Aux Feedback rises above
this level for more than the Q6-26 time, PI Aux Control is
deactivated causing it to have no effect on the output frequency.
For Normal Acting (Q6-23 = 0):
When the PI Aux Feedback rises above this level for more than
the Q6-26 time, PI Aux Control is activated allowing it to affect
the output frequency. When the PI Aux Feedback drops below
this level for more than the Q6-26 time, PI Aux Control is
deactivated causing it to have no effect on the output frequency.
PI Auxiliary Control is always active (if enabled) when set to 0.
Default: 0.0 PSI
Range: 0.0 to
6000.0
–
B.13 Q: PID Controller Parameters
346