![YASKAWA U1000 iQpump Drive Скачать руководство пользователя страница 111](http://html2.mh-extra.com/html/yaskawa/u1000-iqpump-drive/u1000-iqpump-drive_user-manual_3308978111.webp)
No.
Parameter Name
Setting Values
Q4-02
Water Level Scaling
Default: 100 PSI
Minimum: 5
Maximum: 500
Q4-03
Water Level Setpoint
Default: 20.0 ft
Minimum: 0.0
Maximum: 1200.0
Q4-04
Minimum Water Level
Default: 10.0 ft
Minimum: 0.0
Maximum: 1200.0
Q4-05
Water Level Sleep Delay Time
Default: 5 s
Minimum: 0
Maximum: 3600
Q4-06
Wake-Up Water Level
Default: 30.0 ft
Minimum: 0.0
Maximum: 1200.0
Q4-07
Water Level Control Sleep Wake-Up Time
Default: 1 s
Minimum: 0
Maximum: 3600
Q4-08
Level Control Minimum Speed
Default: 0.00 Hz
Minimum: 0.00
Maximum: 400.00
Q4-09
Low Level Detection Level
Default: 0.0 ft
Minimum: 0.0
Maximum: 1200.0
Q4-10
Low Level Detection Time Delay
Default: 0.0
Minimum: 0.0
Maximum: 300.0
Q4-11
Low Level Behavior
Default: 1
Range: 0 to 3
Q4-12
Water Level Control Auto-Restart Time
Default: 5.0 min
Minimum: 0.1
Maximum: 6000.0
Q4-15
Low Water Level Detection Time Unit
Default: 0
Range: 0, 1
U1-01
Frequency Reference
10 V: Maximum frequency
U1-97
Water Level
Full scale:
10 V = Q4-02
4.6 U1000 iQpump Presets and Functions
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
111
4
Start-Up Programming & Operation