No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H2-06
(0437)
Power Consumption
Output Unit Selection
Pwr Mon Unit Sel
Sets the units for the output signal when Power Consumption
Pulse Output or Regenerated Power Pulse Output are selected
as the digital output (H2-01, H2-02, or H2-03 = 39 or 3A).
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Default: 1
Range: 0 to 4
–
H2-07
(0B3A)
MEMOBUS Register 1
Address Select
MFDO Regs1 Addr
Sets the addresses of the MEMOBUS/Modbus registers from
which data will be sent to contact outputs 62 and 162.
Default: 1
Range: 1 to
1FFFH
–
H2-08
(0B3B)
MEMOBUS Register 1
Bit Select
MFDO Regs1 Bit
Sets the bits for the MEMOBUS/Modbus registers from which
data will be sent to contact outputs 62 and 162.
Default: 0
Range: 0 to
FFFFH
–
H2-09
(0B3C)
MEMOBUS Register 2
Address Select
MFDO Regs2 Addr
Sets the addresses of the MEMOBUS/Modbus registers from
which data will be sent to contact outputs 63 and 163.
Default: 1
Range: 1 to
1FFFH
–
H2-10
(0B3D)
MEMOBUS Register 2
Bit Select
MFDO Regs2 Bit
Sets the bits for the MEMOBUS/Modbus registers from which
data will be sent to contact outputs 63 and 163.
Default: 0
Range: 0 to
FFFFH
–
H2 Multi-Function Digital Output Settings
H2-
oo
Setting
Function
LCD Display
Description
Page
0
During run
During RUN 1
Closed: A Run command is active or voltage is output.
–
1
Zero speed
Zero Speed
Open: Output speed is greater than or equal to the value of E1-09 (Minimum Output
Frequency) or b2-01 (DC Injection Braking Start Frequency).
Closed: Output frequency is less than the value of E1-09 (Minimum Output
Frequency) or b2-01 (DC Injection Braking Start Frequency).
–
2
Speed agree 1
Fref/Fout Agree1
Closed: Output frequency equals the speed reference (plus or minus the hysteresis
set to L4-02).
–
3
User-set speed agree 1
Fref/Set Agree 1
Closed: Output frequency and speed reference equal L4-01 (plus or minus the
hysteresis set to L4-02).
–
4
Frequency detection 1
Freq Detect 1
Closed: Output frequency is less than or equal to the value in L4-01 with hysteresis
determined by L4-02.
–
5
Frequency detection 2
Freq Detect 2
Closed: Output frequency is greater than or equal to the value in L4-01 with
hysteresis determined by L4-02.
–
6
Drive ready
Drive Ready
Closed: Power up is complete and the drive is ready to accept a Run command.
–
7
During Power Supply
Voltage Fault
DC Bus Undervolt
Closed: One of the following faults will occur: AUv (Power Supply Undervoltage),
Uv (Undervoltage). or Fdv (Power Supply Frequency Fault).
–
8
During baseblock
(N.O.)
BaseBlk 1
Closed: Drive has entered the baseblock state (no output voltage).
–
9
Frequency reference
source
Ref Source
Open: External Reference 1 or 2 supplies the frequency reference (set in b1-01 or
b1-15).
Closed: Digital operator supplies the frequency reference.
–
A
HAND Mode
Hand Mode
Closed: Pump is in HAND Mode operation.
–
B
Torque detection 1
(N.O.)
Trq Det 1 N.O.
Closed: An overtorque or undertorque situation has been detected.
–
C
Frequency reference
loss
Loss of Ref
Closed: Analog frequency reference has been lost.
Frequency reference loss is detected when the frequency reference drops below
10% of the reference within 400 ms.
–
E
Fault
Fault
Closed: Fault occurred (this excludes CPF00 and CPF01).
–
F
Through mode
Not Used
Select this setting when the terminal is not used or when using the terminal in the
pass-through mode.
–
10
Minor fault
Minor Fault
Closed: An alarm has been triggered.
–
11
Fault reset command
active
Reset Cmd Active
Closed: The drive has received a reset command from the multi-function input
terminals or from a serial network, or the RESET key on the digital operator has
been pressed.
–
12
Timer output
Timer Output
Closed: Timer output.
–
13
Speed agree 2
Fref/Fout Agree2
Closed: When drive output frequency equals the frequency reference ±L4-04.
–
B.8 H Parameters: Multi-Function Terminals
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
305
B
Parameter List