![YASKAWA U1000 iQpump Drive Скачать руководство пользователя страница 84](http://html2.mh-extra.com/html/yaskawa/u1000-iqpump-drive/u1000-iqpump-drive_user-manual_3308978084.webp)
u
Terminal A3 Analog/PTC Input Selection
Terminal A3 can be configured either as multi-function analog input or as PTC input for motor thermal overload protection.
Use switch S4 to select the input function as described in
Table 3.19 DIP Switch S4 Settings
Setting
Description
AI (lower position) (default)
Analog input for the function selected in parameter H3-06
PTC (upper position)
PTC input. Parameter H3-06 must be set to E (PTC input)
3.10 Control I/O Connections
84
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual