No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
F5-09
(03A1)
DO-A3 Output Mode
Selection
DO Function Sel
0: Output terminals are each assigned separate output
functions.
1: Binary code output.
2: Use output terminal functions selected by parameters F5-01
through F5-08.
Default: 0
Range: 0 to 2
–
u
F6: Communication Option Card Settings
Parameters F6-01 through F6-03 and F6-06 through F6-08 are used for DeviceNet and PROFIBUS options. Other parameters
in the F6 group are used for communication-protocol-specific settings. For more details on a specific option card, refer to the
instruction manual for the option.
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
F6-01
(03A2)
Communications Error
Operation Selection
Comm Bus Flt Sel
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0: Ramp to stop. Decelerate to stop using the deceleration time
in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in
C1-09.
3: Alarm only.
Default: 1
Range: 0 to 3
–
F6-02
(03A3)
Pump Fault from Comm.
Option Detection
Selection
EF0 Detection
0: Always Detected
1: Only During Run
0: Always detected.
1: Detection during run only.
Default: 0
Range: 0, 1
–
F6-03
(03A4)
Pump Fault from Comm.
Option Operation
Selection
EF0 Fault Action
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0: Ramp to stop. Decelerate to stop using the deceleration time
in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration time in
C1-09.
3: Alarm only.
Default: 1
Range: 0 to 3
–
F6-04
(03A5)
bUS Error Detection
Time
BUS Err Det Time
Sets the delay time for error detection if a bus error occurs.
Default: 2.0 s
Min.: 0.0
Max.: 5.0
–
F6-07
(03A8)
Multi-Step Speed
Enable/Disable
Selection when NefRef/
ComRef is Selected
Fref PrioritySel
0: Net/Com REF
1: MultiStep Speed
0: Multi-step reference disabled (same as F7)
1: Multi-step reference enabled (same as V7)
Default: 0
Range: 0, 1
–
F6-08
(036A)
Reset Communication
Parameters
Com Prm Init Sel
0: Init Com Prms
1: No Init Com Prms
0: Communication-related parameters (F6-
oo
/F7-
oo
) are
not reset when the drive is initialized using A1-03.
1: Reset all communication-related parameters
(F6-
oo
/F7-
oo
) when the drive is initialized using A1-03.
Default: 0
Range: 0, 1
–
F6-30
(03CB)
PROFIBUS-DP Node
Address
PB Node Address
Sets the node address.
Default: 0
Min.: 0
Max.: 125
–
F6-31
(03CC)
PROFIBUS-DP Clear
Mode Selection
PB Clear Select
0: Reset to Zero
1: Hold Prev Value
0: Resets drive operation with a Clear mode command.
1: Maintains the previous operation state when Clear mode
command is given.
Default: 0
Range: 0, 1
–
F6-32
(03CD)
PROFIBUS-DP Data
Format Selection
PB Map Select
0: PPO Type
1: Conventional
0: PPO Type
1: Conventional
Default: 0
Range: 0, 1
–
F6-50
(03C1)
DeviceNet MAC
Address
DN MAC Address
Selects the drive MAC address.
Default: 64
Min.: 0
Max.: 64
–
F6-51
(03C2)
DeviceNet
Communication Speed
DN Baud Rate
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Set from Network
4: Auto Detect
0: 125 kbps
1: 250 kbps
2: 500 kbps
3: Adjustable from network
4: Detect automatically
Default: 4
Range: 0 to 4
–
F6-52
(03C3) DeviceNet PCA Setting PCA Selection
Sets the format of the data set from the DeviceNet master to
the drive.
Default: 21
Min.: 0
Max.: 255
–
B.7 F: Option Settings
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
295
B
Parameter List