No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H6-04
(042F) Pulse Train Input Bias
Terminal RP Bias
Sets the level of the value selected in H6-01 when 0 Hz is input. Default: 0.0%
Min.: -100.0
Max.: 100.0
–
H6-05
(0430) Pulse Train Input Filter
Time
Term RP Flt Time
Sets the pulse train input filter time constant.
Default: 0.50 s
Min.: 0.00
Max.: 2.00
–
H6-08
(043F)
Pulse Train Input
Minimum Frequency
RP Lower Limit
Sets the minimum frequency for the pulse train input to be
detected. Enabled when H6-01 = 0, 1, or 2.
Default: 0.5 Hz
Min.: 0.1
Max.: 1000.0
–
B.8 H Parameters: Multi-Function Terminals
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
313
B
Parameter List