HOA Keypad Display
Fault Name
Cause
Possible Solution
Option card or hardware is damaged
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
HOA Keypad Display
Fault Name
oFC00
Option Card Connection Error at Option Port CN5-C
Option compatibility error
Cause
Possible Solution
The option card installed into port CN5-C
is incompatible with the drive
Confirm that the drive supports the option card to be installed. Contact Yaskawa for assistance.
A communication option card has been
installed in option port CN5-C
Communication option cards are only supported by option port CN5-A. It is not possible to install more than
one communication option.
HOA Keypad Display
Fault Name
oFC01
Option Card Fault at Option Port CN5-C
Option not properly connected
Cause
Possible Solution
The option card connection to port CN5-C
is faulty.
• Turn the power off and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
• Try to use the card in a different option port. If the option card works properly in a different option port,
CN5-C is damaged, and the drive requires replacement. If the error persists (oFA01 or oFb01 occur),
replace the option card.
HOA Keypad Display
Fault Name
oFC02
Option Card Fault at Option Port CN5-C
Same type of option card is currently connected
Cause
Possible Solution
An option card of the same type is already
installed in option port CN5-A or CN5-B.
Only one of each option card type can only be installed simultaneously. Make sure only one type of option
card is connected.
An input option card is already installed in
option port CN5-A or CN5-B.
Install a communication option, a digital input option, or an analog input option. More than one of the same
type of card cannot be installed simultaneously.
HOA Keypad Display
Fault Name
oFC03 to oFC11
Option Card Error Occurred at Option Port CN5-C
oFC12 to oFC17
Cause
Possible Solution
Option card or hardware is damaged
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
HOA Keypad Display
Fault Name
oFC50 to oFC55
Option Card Error Occurred at Option Port CN5-C
Cause
Possible Solution
Option card or hardware is damaged
Refer to the appropriate option manual for details.
HOA Keypad Display
Fault Name
oH
Heatsink Overheat
The heatsink temperature exceeded the overheat pre-alarm level set to L8-02.
Cause
Possible Solution
Surrounding temperature is too high
• Check the temperature surrounding the drive. Verify temperature is within drive specifications.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool the surrounding area.
• Remove anything near the drive that might be producing excessive heat.
Load is too heavy
• Measure the output current.
• Decrease the load.
• Lower the carrier frequency (C6-02).
5.3 Fault Detection
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
191
5