B.18 V/f Pattern Default Values
show the V/f pattern setting default values depending on the control mode and V/f pattern selection
(A1-02 and E1-03).
Table B.3 E1-03 V/f Pattern Settings for Drive Capacity: Models 4
o
0011 and 4
o
0014
No.
Unit
V/f Control
OLV
E1-03
-
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
60.0
60.0
V
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
V
17.3
17.3
17.3
17.3
40.3
57.5
40.3
57.5
21.9
27.6
21.9
27.6
17.3
17.3
17.3
17.3
13.8
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
V
10.4
10.4
10.4
10.4
9.2
10.4
9.2
10.4
12.7
15.0
12.7
17.3
10.4
10.4
10.4
10.2
2.9
<1> This value determines the default values for E1-04 through E1-10.
<2> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
Table B.4 E1-03 V/f Pattern Settings for Drive Capacity: Models 2
o
0028 to 2
o
0192 and 4
o
0021 to 4
o
0124
No.
Unit
V/f Control
OLV
E1-03
-
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
60.0
60.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
V
16.1
16.1
16.1
16.1
40.3
57.5
40.3
57.5
20.7
26.5
20.7
26.5
16.1
16.1
16.1
16.1
12.7
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
V
8.1
8.1
8.1
8.1
6.9
8.1
6.9
8.1
10.4
12.7
10.4
15.0
8.1
8.1
8.1
8.1
2.3
<1> This value determines the default values for E1-04 through E1-10.
<2> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
Table B.5 E1-03 V/f Pattern Settings for Drive Capacity: Models 2
o
0248 and 4
o
0156 to 4
o
0414
No.
Unit
V/f Control
OLV
E1-03
-
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
60.0
60.0
V
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
230.0
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
3.0
3.0
V
13.8
13.8
13.8
13.8
40.3
57.5
40.3
57.5
17.3
23.0
17.3
23.0
13.8
13.8
13.8
13.8
12.7
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.5
0.5
V
6.9
6.9
6.9
6.9
5.8
6.9
5.8
6.9
8.1
10.4
8.1
12.7
6.9
6.9
6.9
6.9
2.3
<1> This value determines the default values for E1-04 through E1-10.
<2> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
B.18 V/f Pattern Default Values
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual
365
B
Parameter List