B.19 Defaults by Drive Model
The following tables show parameters and default settings that change with the drive model selection (o2-04).
Table B.6 200 V Class Drives Default Settings by Drive Model Selection
No.
Name
Unit
–
Drive Model
–
2
o
0028
2
o
0042
2
o
0054
2
o
0068
o2-04
Drive Model Selection
Hex.
6A
6B
6D
6E
E2-11
Motor Rated Output
kW (HP)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
b3-04
V/f Gain during Speed Search
%
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.5
b8-03
Energy Saving Control Filter Time Constant
s
0.50
0.50
0.50
0.50
b8-04
Energy Saving Coefficient Value
–
72.69
70.44
63.13
57.87
C6-02
Carrier Frequency Selection
–
1
1
1
1
E2-01
Motor Rated Current
A
26.6
39.7
53
65.8
E2-02
Motor Rated Slip
Hz
1.3
1.7
1.6
1.67
E2-03
Motor No-Load Current
A
8
11.2
15.2
15.7
E2-05
Motor Line-to-Line Resistance
Ω
0.288
0.23
0.138
0.101
E2-06
Motor Leakage Inductance
%
15.5
19.5
17.2
20.1
E2-10
Motor Iron Loss for Torque Compensation
W
262
245
272
505
L2-02
Momentary Power Loss Ride-Thru Time
s
0.8
0.9
1
1
L2-03
Momentary Power Loss Minimum Baseblock Time
s
0.3
0.3
0.6
0.6
L2-04
Momentary Power Loss Voltage Recovery Time
s
150
150
150
150
L2-21
Low Input Voltage Detection Level
V
150
150
150
150
L8-02
Overheat Alarm Level
°C
130
130
130
130
L8-35
Installation Method Selection
–
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
Table B.7 200 V Class Drives Default Settings by Drive Model Selection
No.
Name
Unit
–
Drive Model
–
2
o
0081
2
o
0104
2
o
0130
2
o
0154
o2-04
Drive Model Selection
Hex.
6F
70
72
73
E2-11
Motor Rated Output
kW (HP)
22 (30)
30 (40)
37 (50)
45 (60)
b3-04
V/f Gain during Speed Search
%
100
80
80
80
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.5
b8-03
Energy Saving Control Filter Time Constant
s
0.50
0.50
0.50
0.50
b8-04
Energy Saving Coefficient Value
–
51.79
46.27
38.16
35.78
C6-02
Carrier Frequency Selection
–
1
1
1
1
E2-01
Motor Rated Current
A
77.2
105
131
160
E2-02
Motor Rated Slip
Hz
1.7
1.8
1.33
1.6
E2-03
Motor No-Load Current
A
18.5
21.9
38.2
44
E2-05
Motor Line-to-Line Resistance
Ω
0.079
0.064
0.039
0.03
E2-06
Motor Leakage Inductance
%
19.5
20.8
18.8
20.2
E2-10
Motor Iron Loss for Torque Compensation
W
538
699
823
852
L2-02
Momentary Power Loss Ride-Thru Time
s
1
1.1
1.1
1.2
L2-03
Momentary Power Loss Minimum Baseblock Time
s
0.6
0.6
0.6
1
L2-04
Momentary Power Loss Voltage Recovery Time
s
150
150
150
150
L2-21
Low Input Voltage Detection Level
V
150
150
150
150
L8-02
Overheat Alarm Level
°C
130
130
130
130
B.19 Defaults by Drive Model
366
YASKAWA TOEPYAIUPW01A YASKAWA AC Drive - U1000 iQpump Matrix Drive User Manual