Switchgear/Breaker – Manager
Name
Description
Assignment via
SCmd OFF-I
State of the module input: Switching OFF Command,
e.g. the state of the Logics or the state of the digital
input
[Control
/SG
/SG[4]
/Ex ON/OFF Cmd]
Signals of a Controlled Disconnector
Signal
Description
SI SingleContactInd
Signal: The Position of the Switchgear is detected by one auxiliary contact
(pole) only. Thus indeterminate and disturbed Positions cannot be detected.
Pos not ON
Signal: Pos not ON
Pos ON
Signal: Circuit Breaker is in ON-Position
Pos OFF
Signal: Circuit Breaker is in OFF-Position
Pos Indeterm
Signal: Circuit Breaker is in Indeterminate Position
Pos Disturb
Signal: Circuit Breaker Disturbed - Undefined Breaker Position. The Position
Indicators contradict themselves. After expiring of a supervision timer this
signal becomes true.
Pos
Signal: Circuit Breaker Position (0 = Indeterminate, 1 = OFF, 2 = ON, 3 =
Disturbed)
Ready
Signal: Circuit breaker is ready for operation.
t-Dwell
Signal: Dwell time
Removed
Signal: The withdrawable circuit breaker is Removed
Interl ON
Signal: One or more IL_On inputs are active.
Interl OFF
Signal: One or more IL_Off inputs are active.
CES succesf
Signal: Command Execution Supervision: Switching command executed
successfully.
CES Disturbed
Signal: Command Execution Supervision: Switching Command unsuccessful.
Switchgear in disturbed position.
CES Fail TripCmd
Signal: Command Execution Supervision: Command execution failed
because trip command is pending.
CES SwitchDir
Signal: Command Execution Supervision respectively Switching Direction
Control: This signal becomes true, if a switch command is issued even
though the switchgear is already in the requested position. Example: A
switchgear that is already OFF should be switched OFF again (doubly). The
same applies to CLOSE commands.
CES ON d OFF
Signal: Command Execution Supervision: On Command during a pending
OFF Command.
CES SG not ready
Signal: Command Execution Supervision: Switchgear not ready
CES Fiel Interl
Signal: Command Execution Supervision: Switching Command not executed
because of field interlocking.
CES SyncTimeout
Signal: Command Execution Supervision: Switching Command not
executed. No Synchronization signal while t-sync was running.
CES SG removed
Signal: Command Execution Supervision: Switching Command unsuccessful,
Switchgear removed.
Prot ON
Signal: ON Command issued by the Prot module
579
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...