Protective Elements
Parameter
Description
Setting range
Default
Menu path
ExBlo Fc
Activate (allow) or inactivate (disallow)
blocking of the module/stage. This
parameter is only effective if a signal is
assigned to the corresponding global
protection parameter. If the signal becomes
true, those modules/stages are blocked that
are parameterized "ExBlo Fc=active".
inactive,
active
inactive
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
Blo TripCmd
Permanent blocking of the Trip Command of
the module/stage.
inactive,
active
inactive
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
ExBlo TripCmd
Fc
Activate (allow) or inactivate (disallow)
blocking of the module/stage. This
parameter is only effective if a signal is
assigned to the corresponding global
protection parameter. If the signal becomes
true, those modules/stages are blocked that
are parameterized "ExBlo TripCmd
Fc=active".
inactive,
active
inactive
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
I2>
The Threshold setting defines a minimum
operating current magnitude of I2 for the 46
function to operate, which ensures that the
relay has a solid basis for initiating a current
unbalance trip. This is a supervisory function
and not a trip level.
Only available if: I2>.CurrentBase = Device
Rating
0.01 - 4.00In
0.01In
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
I2/FLA
Generator/motor unbalance current pickup
value based on the full load current(FLA)
(Setting from Continuous Unbalance Current
Capability)
Only available if: I2>.CurrentBase =
Protected Object Rating
0.000 - 1.000Ib 0.08Ib
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
%(I2/I1)
The %(I2/I1) setting is the unbalance trip
pickup setting. It is defined by the ratio of
negative sequence current to positive
sequence current (% Unbalance=I2/I1).
Phase sequence will be taken into account
automatically.
inactive,
active
inactive
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
747
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...