Protective Elements
Parameter
Description
Setting range
Default
Menu path
%(I2/I1)
The %(I2/I1) setting is the unbalance trip
pickup setting. It is defined by the ratio of
negative sequence current to positive
sequence current (% Unbalance=I2/I1).
Phase sequence will be taken into account
automatically.
Only available if: %(I2/I1) = use
2 - 40%
20%
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
Char
Characteristic
DEFT,
INV
DEFT
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
t
Tripping delay
Only available if: Characteristic = DEFT
0.00 - 300.00s
0.00s
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
K
This setting is the negative sequence
capability constant. This value is normally
provided by the generator manufacturer.
Only available if: Characteristic = INV
1.00 - 200.00s
10.0s
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
τ-cool
If the unbalanced load current falls below
the pickup value, the cooling-off time is
taken into account. If the unbalanced load
exceeds the pickup value again, than the
saved heat within the electrical equipment
will lead to an accelerated trip.
Only available if: Characteristic = INV
0.0 - 60000.0s
0.0s
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
Current Unbalance Module Input States
Name
Description
Assignment via
ExBlo1-I
Module input state: External blocking1
[Protection Para
/Global Prot Para
/I-Prot
/I2>[1]]
ExBlo2-I
Module input state: External blocking2
[Protection Para
/Global Prot Para
/I-Prot
/I2>[1]]
748
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...