General Lists
Name
Description
UFLS.AdaptSet3-I
Module input state: Adaptive Parameter3
UFLS.AdaptSet4-I
Module input state: Adaptive Parameter4
UFLS.AdaptSet5-I
Module input state: Adaptive Parameter5
AR.active
Signal: active
AR.ExBlo
Signal: External Blocking
AR.Standby
Signal: Standby
AR.t-Blo after CB man
ON
Signal: AR blocked after circuit breaker was switched on manually. This timer will be
started if the circuit breaker was switched on manually. While this timer is running,
AR cannot be started.
AR.Ready
Signal: Ready to shoot
AR.running
Signal: Auto Reclosing running
AR.t-dead
Signal: Dead time between trip and reclosure attempt
AR.CB ON Cmd
Signal: CB switch ON Command
AR.t-Run2Ready
Signal: Examination Time: If the Circuit Breaker remains after a reclosure attempt for
the duration of this timer in the Closed position, the AR has been successful and the
AR module returns into the ready state.
AR.Lock
Signal: Auto Reclosure is locked out
AR.t-Reset Lockout
Signal: Delay Timer for resetting the AR lockout. The reset of the AR lockout state
will be delayed for this time, after the reset signal (e.g digital input or Scada) has
been detected .
AR.Blo
Signal: Auto Reclosure is blocked
AR.t-Blo Reset
Signal: Delay Timer for resetting the AR blocking. The release (de-blocking) of the AR
will be delayed for this time, if there is no blocking signal anymore.
AR.successful
Signal: Auto Reclosing successful
AR.failed
Signal: Auto Reclosing failure
AR.t-AR Supervision
Signal: AR Supervision
AR.Pre Shot
Pre Shot Control
AR.Shot 1
Shot Control
AR.Shot 2
Shot Control
AR.Shot 3
Shot Control
AR.Shot 4
Shot Control
AR.Shot 5
Shot Control
AR.Shot 6
Shot Control
AR.Service Alarm 1
Signal: AR - Service Alarm 1, too many switching operations
AR.Service Alarm 2
Signal: AR - Service Alarm 2 - too many switching operations
AR.Max Shots / h
exceeded
Signal: The maximum allowed number of shots per hour has been exceeded.
AR.Res Statistics Cr
Signal: Reset all statistic AR counters: Total number of AR, successful and
unsuccessful no of AR.
AR.Res Service Cr
Signal: Reset the Service Counters for Alarm and Blocking
AR.Reset Lockout
Signal: The AR Lockout has been reset via the panel.
AR.Res Max Shots / h
Signal: The Counter for the maximum allowed shots per hour has been reset.
AR.ExBlo1-I
Module input state: External blocking1
1193
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...