Supervision
How to set up the Loss of Potential (Evaluating Measured Quantities)
Set the Alarm Time Delay »t-Alarm«.
To prevent a malfunction of the VT supervision for a system fault assign Alarms of overcurrent elements that
should block the Loss of Potential element.
It is necessary to set the parameter »
LOP.LOP Blo Enable« to »active«. Otherwise the Measuring circuit
supervision cannot block elements in case of a loss of potential.
How to make the Loss of Potential (Evaluating Measured Quantities) effective
The Loss of Potential respectively measuring circuit supervision can be used to block protective elements like
undervoltage protection in order to prevent faulty tripping.
Set the parameter »
Measuring Circuit Supervision=active« within those protective elements that should be
blocked by the Loss of Potential supervision.
1081
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...