Protective Elements
Commissioning: Negative Sequence Overcurrent
Object to be tested
Signals to be measured for each current protection function: the threshold values, total tripping time
(recommended), or alternatively tripping delays and the dropout ratios.
It is recommended to measure the total tripping time instead of the tripping
time. The tripping delay should be specified by the customer. The total tripping
time is measured at the position signalling contacts of the CBs (not at the relay
output!).
Total tripping time: = tripping delay (please refer to the tolerances of the
protection stages) + CB operating time (about 50 ms)
Please take the CB switching times from the technical data, specified in the
relevant documentation, provided by the CB manufacturer.
Necessary means:
Current source
Current meters
Timer
Procedure:
Testing the threshold values
In order to get a
negative-sequence
current, please change the phase sequence at the terminals of the current
source (in case of ABC sequence to ACB – in case of a ACB sequence to ABC).
For each test performed, feed a current that is about 3-5% above the threshold value for activation/tripping. Then
check the threshold values.
Testing the total tripping delay (recommendation)
Measure the total tripping times at the auxiliary contacts of the breakers (breaker tripping).
Testing the tripping delay
(measuring at the relay output contact)
Measure the tripping times at the relay output contact.
Testing the dropout ratio
Reduce the current to 97% below the trip value and check the
dropout
ratio.
Successful test result
The measured total tripping delays or individual tripping delays, threshold values, and
dropout
ratios correspond
with those values specified in the adjustment list. Permissible deviations/tolerances can be found under Technical
Data.
709
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...