Protective Elements
Auto Reclosure controlled LVRT
In case that the
LVRT should be able to ride through auto reclosures, the parameter »ARControlledLVRT« has to
be set to »
active«.
In order to supervise the Low Voltage Ride Through events during reclosure, the user has to set the supervision
timer »tLVRT
« at least equal or greater than the complete Multi-Shot AR-runtime. In addition to that the number of
permitted
LVRTs has to be set whichis usually the number of auto reclosure attempts. The actual LVRT supervision
will be controlled to ride through the preset
LVRT voltage pattern. By reaching the preset number of LVRT events
»
NumberOfLVRT«, the actual LVRT supervision assumes that the detected system fault is permanent, ignores the
voltage profile and issues a tripping command instantaneously in order to disconnect the distributed resource from
the electrical power system.
965
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...