Input, Output and LED Settings
Input, Output and LED Settings
Configuration of the Digital Inputs
Set the following parameters for each of the digital inputs:
»Nominal voltage«
»Debouncing time«: A state change will only be adopted by the digital input after the debouncing time has
expired.
»Inverting« (where necessary)
The debouncing time will be started each time the state of the input signal
alternates.
In addition to the debouncing time that can be set via software, there is always
a hardware debouncing time (approx 12 ms) that cannot be turned of.
96
MCDLV4
DOK-HB-MCDLV4-2E
=1
State of the digital input
Inverting
Input Signal
Nom voltage
0
t
Debouncing time
DI Slot X.DI x
active
Inverting
inactive
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...