General Lists
Name
Description
SG[5].ON Cmd
Signal: ON Command issued to the switchgear. Depending on the setting the signal
may include the ON command of the Prot module.
SG[5].OFF Cmd
Signal: OFF Command issued to the switchgear. Depending on the setting the signal
may include the OFF command of the Prot module.
SG[5].ON Cmd manual
Signal: ON Cmd manual
SG[5].OFF Cmd manual
Signal: OFF Cmd manual
SG[5].Sync ON request
Signal: Synchronous ON request
SG[5].Aux ON-I
Module Input State: Position indicator/check-back signal of the CB (52a)
SG[5].Aux OFF-I
Module input state: Position indicator/check-back signal of the CB (52b)
SG[5].Ready-I
Module input state: CB ready
SG[5].Sys-in-Sync-I
State of the module input: This signals has to become true within the synchronization
time. If not, switching is unsuccessful.
SG[5].Removed-I
State of the module input: The withdrawable circuit breaker is Removed
SG[5].Ack TripCmd-I
State of the module input: Acknowledgement Signal (only for automatic
acknowledgement) Module input signal
SG[5].Interl ON1-I
State of the module input: Interlocking of the ON command
SG[5].Interl ON2-I
State of the module input: Interlocking of the ON command
SG[5].Interl ON3-I
State of the module input: Interlocking of the ON command
SG[5].Interl OFF1-I
State of the module input: Interlocking of the OFF command
SG[5].Interl OFF2-I
State of the module input: Interlocking of the OFF command
SG[5].Interl OFF3-I
State of the module input: Interlocking of the OFF command
SG[5].SCmd ON-I
State of the module input: Switching ON Command, e.g. the state of the Logics or the
state of the digital input
SG[5].SCmd OFF-I
State of the module input: Switching OFF Command, e.g. the state of the Logics or
the state of the digital input
SG[5].Operations Alarm Signal: Service Alarm, too many Operations
SG[5].Isum Intr trip: IL1
Signal: Maximum permissible Summation of the interrupting (tripping) currents
exceeded: IL1
SG[5].Isum Intr trip: IL2
Signal: Maximum permissible Summation of the interrupting (tripping) currents
exceeded: IL2
SG[5].Isum Intr trip: IL3
Signal: Maximum permissible Summation of the interrupting (tripping) currents
exceeded: IL3
SG[5].Isum Intr trip
Signal: Maximum permissible Summation of the interrupting (tripping) currents
exceeded in at least one phase.
SG[5].Res TripCmd Cr
Signal: Resetting of the Counter: total number of trip commands
SG[5].Res Sum trip
Signal: Reset summation of the tripping currents
SG[5].WearLevel Alarm
Signal: Threshold for the Alarm
SG[5].WearLevel
Lockout
Signal: Threshold for the Lockout Level
SG[5].Res CB OPEN
capacity
Signal: Reset of the wear maintenance curve (i. e. of the counter for the Circuit
Breaker OPEN capacity.
SG[5].Isum Intr ph Alm
Signal: Alarm, the per hour Sum (Limit) of interrupting currents has been exceeded.
SG[5].Res Isum Intr ph
Alm
Signal: Reset of the Alarm, "the per hour Sum (Limit) of interrupting currents has
been exceeded".
1167
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...