Protective Elements
Setting Group Parameters of the Synchrocheck Fault Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of
module/stage.
inactive,
active
inactive
[Protection
Para
/<1..4>
/Intercon-Prot
/Sync
/General
Settings]
ExBlo Fc
Activate (allow) or inactivate (disallow)
blocking of the module/stage. This
parameter is only effective if a signal is
assigned to the corresponding global
protection parameter. If the signal becomes
true, those modules/stages are blocked that
are parameterized "ExBlo Fc=active".
inactive,
active
inactive
[Protection
Para
/<1..4>
/Intercon-Prot
/Sync
/General
Settings]
Bypass Fc
Allowing to bypass the Synchrocheck, if the
state signal that is assigned to the
parameter with the same name within the
Global Parameters (logic input) becomes
true.
inactive,
active
inactive
[Protection
Para
/<1..4>
/Intercon-Prot
/Sync
/General
Settings]
SyncMode
Synchrocheck mode: GENERATOR2SYSTEM
= Synchronizing generator to system
(breaker close initiate needed).
SYSTEM2SYSTEM = SynchronCheck between
two systems (Stand-Alone, no breaker info
needed)
System2System
,
Generator2Syst
em
System2Syste
m
[Protection
Para
/<1..4>
/Intercon-Prot
/Sync
/Mode / Times]
t-
MaxCBCloseDel
ay
Maximum circuit breaker close time delay
(Only used for GENERATOR-SYSTEM working
mode and is critical for a correct
synchronized switching)
Only available if: SyncMode =
System2System
0.00 - 300.00s
0.05s
[Protection
Para
/<1..4>
/Intercon-Prot
/Sync
/Mode / Times]
t-
MaxSyncSuperv
Synchron-Run timer: Max. time allowed for
synchronizing process after a close initiate.
Only used for GENERATOR2SYSTEM working
mode.
Only available if: SyncMode =
System2System
0.00 - 3000.00s 30.00s
[Protection
Para
/<1..4>
/Intercon-Prot
/Sync
/Mode / Times]
889
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...