Field Parameters
Parameter
Description
Setting range
Default
Menu path
Phase MTA
Maximum Torque Angle: Angle between
phase current and reference voltage in case
of a short circuit. This angle is needed to
determine the fault direction in case of short
circuits.
0 - 360°
45°
[Field Para
/Direction]
IG calc dir ctrl
Options for direction detection. IGcalc is
used as operating quantity.
IG calc 3V0,
IG calc IPol (IG
meas),
Dual,
I2,V2
IG calc 3V0
[Field Para
/Direction]
IG meas dir ctrl Options for direction detection. IGmeas is
used as operating quantity.
IG meas 3V0,
I2,V2,
Dual
IG meas 3V0
[Field Para
/Direction]
3V0 Source
Earth overcurrent protection elements take
into account this parameter for direction
decisions. You have to ensure, that this
parameter is set to "Measured" only if the
residual voltage is fed to the fourth
measuring input of the voltage measuring
card.
measured,
calculated
measured
[Field Para
/Direction]
Ground MTA
Ground Maximum Torque Angle: Angle
between chosen operating quantity and
chosen reference quantity in case of a
ground fault. This angle is needed to
determine the ground fault direction in case
of a short circuit. Depending on the selected
ground direction option, different MTA
values are used: IGcalc 3V0, IGmeas 3V0 :
Ground MTA; IGcalc Neg, IGmeas Neg : 90°
+ Phase MTA; IGcalc IPol : 0°; IGcalc Dual :
0° (if I2 and V2 available) or Ground MTA;
IGmeas Dual : 90° + Phase MTA (if I2 and
V2 available) or Ground MTA.
0 - 360°
110°
[Field Para
/Direction]
ECT Angle Cor
Fine adjustment of the measuring angle of
the earth current transformers. By means of
the Angle Correction, faults of the earth
voltage transformers can be taken into
account.
-45 - 45°
0°
[Field Para
/Direction]
466
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...