Time Synchronization
Fault Analysis
If there is no SNTP signal for more than 120 sec, the SNTP status changes from “active” to “inactive” and an entry
in the Event Recorder will be created.
The SNTP functionality can be checked in the menu
[Operation/Status Display/TimeSync/Sntp]
:
If the SNTP status is not indicated as being “active”, please proceed as follows:
Check if the wiring is correct (Ethernet-cable connected).
Check if a valid IP address is set in the device (Device Para/TCP/IP).
Check if the IP address of the SNTP server is set in the device (Device Para/ Time/ TimeSync/ SNTP).
Check if SNTP is used for time synchronization (Device Para/ Time/ TimeSync/ TimeSync).
Check if the Ethernet connection is active (Device Para/TCP/IP/Link = Up?).
Check if both the SNTP server and the protection device answer to a Ping.
Check if the SNTP server is up and working.
403
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...