Input, Output and LED Settings
Parameter
Description
Setting range
Default
Menu path
Debouncing
time 8
A change of the state of a digital input will
only be recognized after the debouncing
time has expired (become effective). Thus,
transient signals will not be misinterpreted.
8
no debouncing
time,
20 ms,
50 ms,
100 ms
no
debouncing
time
[Device Para
/Digital Inputs
/DI Slot X5
/Group 1]
105
MCDLV4
DOK-HB-MCDLV4-2E