General Lists
Name
Description
SG[3].Res CB OPEN
capacity
Signal: Reset of the wear maintenance curve (i. e. of the counter for the Circuit
Breaker OPEN capacity.
SG[3].Isum Intr ph Alm
Signal: Alarm, the per hour Sum (Limit) of interrupting currents has been exceeded.
SG[3].Res Isum Intr ph
Alm
Signal: Reset of the Alarm, "the per hour Sum (Limit) of interrupting currents has
been exceeded".
SG[4].SI
SingleContactInd
Signal: The Position of the Switchgear is detected by one auxiliary contact (pole)
only. Thus indeterminate and disturbed Positions cannot be detected.
SG[4].Pos not ON
Signal: Pos not ON
SG[4].Pos ON
Signal: Circuit Breaker is in ON-Position
SG[4].Pos OFF
Signal: Circuit Breaker is in OFF-Position
SG[4].Pos Indeterm
Signal: Circuit Breaker is in Indeterminate Position
SG[4].Pos Disturb
Signal: Circuit Breaker Disturbed - Undefined Breaker Position. The Position Indicators
contradict themselves. After expiring of a supervision timer this signal becomes true.
SG[4].Ready
Signal: Circuit breaker is ready for operation.
SG[4].t-Dwell
Signal: Dwell time
SG[4].Removed
Signal: The withdrawable circuit breaker is Removed
SG[4].Interl ON
Signal: One or more IL_On inputs are active.
SG[4].Interl OFF
Signal: One or more IL_Off inputs are active.
SG[4].CES succesf
Signal: Command Execution Supervision: Switching command executed successfully.
SG[4].CES Disturbed
Signal: Command Execution Supervision: Switching Command unsuccessful.
Switchgear in disturbed position.
SG[4].CES Fail TripCmd
Signal: Command Execution Supervision: Command execution failed because trip
command is pending.
SG[4].CES SwitchDir
Signal: Command Execution Supervision respectively Switching Direction Control:
This signal becomes true, if a switch command is issued even though the switchgear
is already in the requested position. Example: A switchgear that is already OFF
should be switched OFF again (doubly). The same applies to CLOSE commands.
SG[4].CES ON d OFF
Signal: Command Execution Supervision: On Command during a pending OFF
Command.
SG[4].CES SG not ready Signal: Command Execution Supervision: Switchgear not ready
SG[4].CES Fiel Interl
Signal: Command Execution Supervision: Switching Command not executed because
of field interlocking.
SG[4].CES SyncTimeout Signal: Command Execution Supervision: Switching Command not executed. No
Synchronization signal while t-sync was running.
SG[4].CES SG removed
Signal: Command Execution Supervision: Switching Command unsuccessful,
Switchgear removed.
SG[4].Prot ON
Signal: ON Command issued by the Prot module
SG[4].TripCmd
Signal: Trip Command
SG[4].Ack TripCmd
Signal: Acknowledge Trip Command
SG[4].ON incl Prot ON
Signal: The ON Command includes the ON Command issued by the Protection
module.
SG[4].OFF incl TripCmd
Signal: The OFF Command includes the OFF Command issued by the Protection
module.
SG[4].Position Ind
manipul
Signal: Position Indicators faked
1164
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...