Parameters
Application Examples
•
The output signal of the
Switch Onto Fault module can be used to activate an Adaptive Parameter Set that
sensibilizes the overcurrent protection.
•
The output signal of the
Cold Load Pickup module can be used to activate an Adaptive Parameter Set that
desensitizes the overcurrent protection.
•
By means of
Adaptive Parameter Sets an Adaptive Auto Reclosure can be realized. After a reclosure
attempt the tripping thresholds or tripping curves of the overcurrent protection can be adapted.
•
Depending on undervoltage the overcurrent protection can be modified (Voltage Controlled).
•
The earth overcurrent protection can be modified by the residual voltage.
•
Matching the ground current protective settings dynamically and automatically according to the single-
phase load diversity (Adaptive relay Setting – Normal Setting/Alternative Setting)
Adaptive Parameter Sets are only available for devices with current protection
modules.
419
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...