Input, Output and LED Settings
Parameter
Description
Setting range
Default
Menu path
Force OR4
By means of this function the normal Output
Relay State can be overwritten (forced). The
relay can be set from normal operation
(relay works according to the assigned
signals) to "force energized" or "force de-
energized" state.
Normal,
De-Energized,
Energized
Normal
[Service
/Test (Prot
inhibit)
/Force OR
/BO Slot X4]
Force OR5
By means of this function the normal Output
Relay State can be overwritten (forced). The
relay can be set from normal operation
(relay works according to the assigned
signals) to "force energized" or "force de-
energized" state.
Normal,
De-Energized,
Energized
Normal
[Service
/Test (Prot
inhibit)
/Force OR
/BO Slot X4]
Device Parameters of the Binary Output Relays on OR-5 X
Parameter
Description
Setting range
Default
Menu path
Operating Mode Operating Mode
Working
current
principle,
Closed-circuit
principle
Working
current
principle
[Device Para
/Binary Outputs
/BO Slot X4
/BO 1]
t-hold
To clearly identify the state transition of a
binary output relay, the "new state" is being
hold, at least for the duration of the hold
time.
0.00 - 300.00s
0.00s
[Device Para
/Binary Outputs
/BO Slot X4
/BO 1]
t-Off Delay
Switch Off Delay
0.00 - 300.00s
0.00s
[Device Para
/Binary Outputs
/BO Slot X4
/BO 1]
Latched
Defines whether the Relay Output will be
latched when it picks up.
inactive,
active
inactive
[Device Para
/Binary Outputs
/BO Slot X4
/BO 1]
Acknowledgem
ent
Acknowledgement Signal - An
acknowledgement signal (that
acknowledges the corresponding binary
output relay) can be assigned to each
output relay. The acknowledgement-signal
is only effective if the parameter "Latched"
is set to active.
Only available if: Latched = active
1..n,
Assignment List
-.-
[Device Para
/Binary Outputs
/BO Slot X4
/BO 1]
135
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...