Protective Elements
IEC Long Time Inverse
Various reset modes are available:
Resetting via characteristic, delayed and instantaneous.
Remark: For
I > 20⋅I
>
, the curve stops decreasing, the t-values are kept constant at the value for
I = 20⋅I
>
.
684
MCDLV4
DOK-HB-MCDLV4-2E
0.01
0.1
1
10
100
0.1
1
10
100
1000
0.05
0.1
0.2
0.5
1
1.5
t [s]
I / I> (multiples of pickup)
tchar=
P
d
o
c_
Z
0
3
Reset
Trip
»Char«
= IEC LINV
≤ 20
t
− 1
120
=
I
I>
If:
I
I>
1 <
tchar
t
1−
120
=
I
I>
2
If:
< 1
I
I>
tchar
Содержание HighPROtec MCDLV4