Protective Elements
6
Lockout
An activated autoreclose function goes into the »L
OCKOUT
« state when one of the following conditions is true:
An unsuccessful autoreclose is detected after all programmed autoreclose shots. The fault is of permanent
nature.
Reclose failure (incomplete sequence)
Autoreclose rate per hour exceeds the limit
Fault timer elapses (tripping time too long)
Breaker failure during AR starting
Manual breaker close operation during autoreclose process
At least one protective function is still tripping before reclose command is issued
The autoreclose function exits the »L
OCKOUT
« state if the programmed lockout reset signal asserts and programmed
Lockout Reset timer elapses.
A Service Alarm (Service Alarm 1 or Service Alarm 2) will not lead to a lockout of the
AR function.
787
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...