62
Computing the Cycle Time
Section 2-7
5: Peripheral Servicing
2-7-3
Functions Related to the Cycle Time
Minimum Cycle Time
Set the minimum cycle time to a non-zero value to eliminate inconsistencies in
I/O responses. A minimum cycle time can be set in the PLC Setup between 1
and 32,000 ms in 1-ms increments.
This setting is effective only when the actual cycle time is shorter than the
minimum cycle time setting. If the actual cycle time is longer than the mini-
mum cycle time setting, the actual cycle time will remain unchanged.
PLC Setup
Details
Processing time and fluctuation cause
Services Ethernet port.
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 8% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If the ports are not connected, the servicing time is 0 ms.
Services serial ports
Services communications ports.
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 8% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If no communications ports are used, the servicing time is 0 ms.
Services built-in flash memory access.
If a uniform peripheral servicing time hasn’t been set in the PLC Setup for
this servicing, 8% of the previous cycle’s cycle time (calculated in step (3))
will be allowed for peripheral servicing.
If a uniform peripheral servicing time has been set in the PLC Setup, servic-
ing will be performed for the set time. Servicing will be performed for at
least 0.1 ms, however, whether the peripheral servicing time is set or not.
If there is no access, the servicing time is 0 ms.
Serves Memory Cassette access.
Minimum cycle time
(effective)
Minimum cycle time
(effective)
Minimum cycle time
(effective)
Actual cycle
time
Actual cycle
time
Actual cycle
time
Minimum cycle time
Actual cycle
time
Minimum cycle time
Actual cycle
time
Minimum cycle time (effective)
Actual cycle
time
Name
Settings
Default
Minimum cycle time
0000 to 7D00 hex
(1 to 32,000 ms in 1-ms incre-
ments)
0000 hex: Variable cycle time
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......