495
Analog I/O Units
Section 9-4
Reading Analog Input Converted Values
The ladder program can be used to read the memory area words where the
converted values are stored. Values are output to the next two words (m + 1,
m + 2) following the last input word (m) allocated to the CPU Unit or previous
Expansion Unit or Expansion I/O Unit.
Writing Analog Output Converted Values
The ladder program can be used to write data to the memory area where the
set value is stored. The output word will be “n+1,” where “n” is the last output
word allocated to the CPU Unit or previous Expansion Unit or Expansion I/O
Unit.
Startup Operation
After power is turned ON, it will require two cycle times plus approx. 50 ms
before the first data is converted. The following instructions can be placed at
the beginning of the program to delay reading converted data from analog
inputs until conversion is actually possible.
Analog input data will be 0000 until initial processing has been completed.
Analog output data will be 0 V or 0 mA until the range code has been written.
After the range code has been written, the analog output data will be 0 V or
0 mA if the range is 0 to 10 V,
−
10 to 10 V, or 0 to 20 mA, or it will be 1 V or
4 mA if the range is 1 to 5 V or 4 to 20 mA.
Handling Unit Errors
• When an error occurs in the Analog I/O Unit, analog input data will be
0000 and 0 V or 0 mA will be output as the analog output.
If a CPU error or an I/O bus error (fatal errors) occurs at the CPU Unit and
the analog output is set to 1 to 5 V or 4 to 20 mA, 0 V or 0 mA will be out-
put. For any other fatal errors at the CPU Unit, 1 V or 4 mA will be output.
• CP-series Expansion Unit or Expansion I/O Unit errors are output to bits
0 to 5 of word A436. The bits are allocated from A436.00 in order starting
with the Unit nearest the CPU Unit. Use these flags in the program when
it is necessary to detect errors.
Program Example
This programming example uses these ranges:
Analog input 0: 0 to 10 V
Analog input 1: 4 to 20 mA
Analog output: 0 to 10 V
MOV(021)
2
D0
Always ON Flag
P_On
0005
TIM
#0002
T0005
TIM 0005 will start as soon as power turns
ON. After 0.2 s (200 ms), the input for TIM
0005 will turn ON, and the converted data
from analog input 0 that is stored in word 2
will be transferred to D0.
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......