![background image](http://html1.mh-extra.com/html/omron/cp1l-el20dr-d/cp1l-el20dr-d_operation-manual_743755404.webp)
370
Inverter Positioning
Section 7-3
Referencing the
Automatically Calculated
Inverter Frequency
Command Value
If the following settings are made in the PLC Setup, the inverter frequency
command value will be calculated automatically and set in A23 in the Auxiliary
Area. These settings are on the Inverter Positioning 0 Tab Page in the PLC
Setup.
• Power Supply Frequency for One Motor Revolution per Second (0.1-Hz
increments)
• Number of Encoder Pulses for One Motor Revolution
• Error Counter Cycle (x 4 ms)
The inverter frequency command value in A23 is accessed and converted to
an analog output signal. The CP1W-DA041 has a resolution of 6,000, so the
conversion to an analog signal is performed as follows:
6,000
÷
60 Hz (inverter’s maximum output frequency)
÷
100 = 1
The conditions are as follows:
In this example, the results of *U and /UL are 1, so the value in A23 is moved
directly to D102 with MOV.
Error counter
Operation
Inverter
Inductive motor
Encoder
Outputs not
accepted
Forward/Reverse Command
Bit turned ON.
The contents of D102 is set in D1020.
Analog
conversion
trigger
Operation
Command Bit
Operation
Command Bit
A26.00
In-position Flag
Forward
Command Bit
A26.01
Forward
Command Bit
Reverse
Command Bit
T0
T0
T0
A26.00
A26.01
A26.02
A26.03
100.02
100.03
The frequency command value is divided by
100 to convert to Hz and stored in D1020.
To convert to the analog output value, the inverter
frequency command value is multiplied by 100
(analog resolution of 6,000 divided by inverter's
maximum frequency of 60) and stored in D1010
and D1011.
An analog value of 0 for the
stop command set in D102.
*U
A023
&100
D1010
/U
D1010
&100
D1020
MOV
#0000
D102
MOV
D1020
D102
Always ON Flag
P_On
TIM
0
#0003
Time for data for Analog Output Unit to become valid.
Analog
conversion
trigger
Analog
conversion
trigger
Reverse
Command Bit
A26.02
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......