440
Memory Cassette Functions
Section 8-6
3.
Open the cover for the CPU Unit's battery and set DIP switch pin SW2 to
ON.
4.
Turn ON the power supply to the CPU Unit.
5.
The automatic transfer from the Memory Cassette will begin. The rest of
the procedure assumes that the operating mode after automatic transfer at
startup to PROGRAM mode (default).
6.
After the automatic transfer has been completed, turn OFF the power sup-
ply to the CPU Unit.
7.
Remove the Memory Cassette, and replace the Memory Cassette slot cover.
8.
Return the setting of DIP switch pin SW2 to OFF, and close the cover.
9.
Turn the power supply to the CPU Unit back ON.
Note
After the automatic transfer from the Memory Cassette at startup has been
completed with the operating mode after automatic transfer at startup set to
PROGRAM mode (default), the transfer will not start again automatically
(regardless of the Startup Mode setting in the PLC Setup). As described in the
procedure above, to start operation turn the power supply OFF, return the set-
ting of DIP switch SW2 to OFF, and then turn the power supply back ON. If the
the operating mode specified in the PLC Setup is set as the operating mode
after automatic transfer at startup, operation will start without changing the
DIP switch SW2 or Memory Cassette.
Operating from a
Memory Cassette
1,2,3...
1.
Prepare a Memory Cassette containing the required data.
When transferring the data to the Memory Cassette, set the operating
mode after automatic transfer at startup to PROGRAM mode (default).
2.
With the power supply turned OFF to the CPU Unit, remove the cover from
the Memory Cassette slot and insert the Memory Cassette.
3.
Open the cover for the CPU Unit's PERIPHERAL section and set DIP
switch pin SW2 to ON.
4.
Turn ON the power supply to the CPU Unit.
Note
If, when the data is transferred to the Memory Cassette, the operating mode
specified in the PLC Setup is set as the operating mode after automatic trans-
fer at startup, operation will start automatically after data transfer, even if the
power is not cycled. Be sure that starting operation will cause no problems
before using automatic transfer at startup.
NC
POWER
RUN
DIP switch pin
SW2 set to ON.
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......