693
Appendix D
Auxiliary Area Allocations by Address
Read-only Area (Set by System)
Address
Name
Function
Settings
Status
after
mode
change
Status
at star-
tup
Write
timing
Related
flags, set-
tings
Words
Bits
A0
---
10-ms Incre-
menting Free
Running
Timer
This word contains the system timer
used after the power is turned ON.
A value of 0000 hex is set when the
power is turned ON and this value is
automatically incremented by 1
every 10 ms. The value returns to
0000 hex after reaching FFFF hex
(655,350 ms), and then continues to
be automatically incremented by 1
every 10 ms.
Note:
The timer will continue to be
incremented when the operat-
ing mode is switched to RUN
mode.
Example: The interval can be
counted between processing A and
processing B without requiring timer
instructions. This is achieved by
calculating the difference between
the value in A0 for processing A and
the value in A0 for processing B. The
interval is counted in 10 ms units.
---
Retained
Cleared
Every
10 ms after
power is
turned ON
---
A1
---
100-ms Incre-
menting Free
Running
Timer
This word contains the system timer
used after the power is turned ON.
A value of 0000 hex is set when the
power is turned ON and this value is
automatically incremented by 1
every 100 ms. The value returns to
0000 hex after reaching FFFF hex
(6,553,500 ms), and then continues
to be automatically incremented by 1
every 100 ms.
Note:
The timer will continue to be
incremented when the operat-
ing mode is switched to RUN
mode.
Example: The interval can be
counted between processing A and
processing B without requiring timer
instructions. This is achieved by
calculating the difference between
the value in A0 for processing A and
the value in A0 for processing B. The
interval is counted in 100 ms units.
---
Retained
Cleared
Every
100 ms
after power
is turned
ON
---
A20
and
A21
---
Present Value
of Unsigned
Output Value
0
These words contain the present
value of the unsigned output value
(output value = present value of error
counter
×
error counter cycle (s)
×
gain) for inverter positioning 0.
Data range: 0000 0000 to
8000 0000 hex (0 to 2,147,483,648)
The maximum and minimum output
values set for inverter positioning 0 in
the PLC Setup are applied.
A21 contains the leftmost 4 digits
and A20 contains the rightmost 4
digits.
---
---
Cleared
Every error
counter 0
cycle
---
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......