522
Temperature Sensor Units
Section 9-5
Programming with SCL2(
−
) Instruction
Operation
Two-decimal-place
Mode
If pin 2 on the DIP switch is turned ON, values are stored to two decimal
places. In this case, temperature data is stored as 6-digit signed hexadecimal
(binary) data with 4 digits in the integer portion and 2 digits after the decimal
point. The actual data stored in memory is 100 times the actual value, i.e., the
decimal point is not indicated. Methods for handling this data are described in
this section.
Note
When set to store values to two decimal places, temperature data as far as
two digits after the decimal point is converted to 6-digit binary data, but the
actual resolution is not 0.01
°
C (
°
F). For this reason, there may be skipping
and inaccuracies in the first digit after the decimal point (0.1). Treat any reso-
lution above that specified for the normal data format as reference data.
2
#7FFF
1000.00
CMP(020)
1000.00
2
#7FFE
Always ON
P_On
CMP(020)
P_EQ
100.00
P_CY
P_EQ
#0000
D1
MOV(021)
2
D10
SCL2(486)
D0
P_CY
#0001
D1
MOV(021)
ON when initialization complete.
Execution
condition
ON when an open-circuit alarm has
been detected.
Parameter settings for data conversion:
When the converted value is non-
negative, stores #0000 in D1.
When the converted value is
negative, stores #0001 in D1.
Detects completion of input 0
initialization.
Detects an open-circuit alarm or Unit
error by checking whether the error
code 7FFF has been output.
CIO 2
D1
1: Negative, 0: Non-negative
16
3
16
2
16
1
16
0
0
0
0
1/0
1/0
D0
CY
(when using SCL2 instruction)
Binary to BCD conversion
10
3
10
2
10
1
10
0
0: If data non-negative, "0000" stored in D1.
1: If data negative, "0001" stored in D1.
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......