465
Analog Input Units
Section 9-2
Averaging Function
For analog inputs, the averaging function operates when the averaging bit is
set to 1. The averaging function outputs the average (a moving average) of
the last eight input values as the converted value. If there is only a slight vari-
ation in inputs, it is handled by the averaging function as a smooth input.
The averaging function stores the average (a moving average) of the last
eight input values as the converted value. Use this function to smooth inputs
that vary at a short interval.
Open-circuit Detection
Function
The open-circuit detection function is activated when the input range is set to
1 to 5 V and the voltage drops below 0.8 V, or when the input range is set to 4
to 20 mA and the current drops below 3.2 mA. When the open-circuit detec-
tion function is activated, the converted data will be set to 8,000.
The time for enabling or clearing the open-circuit detection function is the
same as the time for converting the data. If the input returns to the convertible
range, the open-circuit detection is cleared automatically and the output
returns to the normal range.
Procedure
Writing Set Data and
Reading A/D Converted
Values
4 mA
20 mA
20.8 mA
3.2 mA
FDA8 (
−
600)
3138 (12600)
2EE0 (12000)
0000 (0)
0 mA
Converted Data
Hexadecimal (Decimal)
Connect and wire Units.
Create a ladder program.
• Connect Analog Input Units.
• Wire to analog output devices.
• Write set data to output words (n+1, n+2).
• Set use of inputs.
• Select input signals using range codes.
• Set use of averaging.
• Read A/D converted values from input words
(m+1 to m+4).
• For current inputs, confirm that there is no open
circuit.
CPU Unit
MOV(021)
Set data (inputs 1, 2)
Set data (inputs 3, 4)
Analog input 3 converted value
Analog input 4 converted value
Analog Input Unit
Ladder program
Analog input 1 converted value
Analog input 2 converted value
Analog devices
Temperature sensor
Pressure sensor
Speed sensor
Flow sensor
Voltage/current meter
Other devices
Writes the set data.
Reads the converted
value.
“m” is the last input word and “n” is
the last output word allocated to the
CPU Unit or previous Expansion
Unit or Expansion I/O Unit.
Word (n+1)
Word (n+2)
Word (m+1)
Word (m+2)
Word (m+3)
Word (m+4)
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......