262
Pulse Outputs
Section 7-2
Operating Mode 1 without Origin Proximity Input Signal Reverse (Origin
Detection Method Setting = 1)
Depending on the length of the deceleration time, the stopping position may
change when the Origin Input Signal is detected during deceleration.
Operating Mode 2 (with Error Counter Reset Output, with Positioning
Completed Input)
This operating mode is the same as mode 1, except the Positioning Com-
pleted Signal (INP) from the Servo Driver is used. Connect the Positioning
Completed Signal from the Servo Driver to a normal input (origin search 0 to 3
input).
1
1
0
0
CCW
CCW
CW
CW
Origin Proximity
Input Signal
Origin Input Signal
(Phase-Z signal)
Pulse output
Verify that the Origin Proximity Input
Signal's dog setting is long enough
(longer than the deceleration time.)
Origin Input
Signal is
ignored during
deceleration.
Motor stopped by an Origin
Input Signal received after
deceleration.
Starts when
ORG(889) is
executed.
Stop
Ideal time for the Origin Proximity Input
Signal to go OFF.
(Settings when the
deceleration time is short)
Stop (See note.)
Starts when ORG(889)
is executed.
Note:
The Origin Input Signal can be detected immediately
after the Origin Proximity Input Signal goes from ON
to OFF if the deceleration time is short, e.g., starting
from within the Origin Proximity Input Signal.
1
1
0
0
CCW
CCW
CW
CW
Origin Proximity
Input Signal
Origin Input Signal
(Phase-Z signal)
(The deceleration time is
relatively long in this case.)
Pulse output
(The deceleration time is short
in this case.)
Origin Input
Signal is
ignored during
deceleration.
Motor stopped by an Origin
Input Signal received after
deceleration.
Starts when
ORG(889) is
executed.
Stop
Motor stopped by an
Origin Input Signal
received after
deceleration.
Starts when
ORG(889)
is executed.
Stop
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......