519
Temperature Sensor Units
Section 9-5
“m” is the last input word allocated to the CPU Unit, Expansion I/O Unit, or
Expansion Unit connected immediately before the Temperature Sensor Unit.
• Negative values are stored as 2’s complements.
• Data for range codes that include one digit after the decimal point are
stored without the decimal point, i.e., 10 times the actual value is stored.
• If the input temperature exceeds the maximum or minimum value in the
temperature input range that has been set by ±20
°
C or ±20
°
F, the dis-
played value will be held.
• If the circuit is disconnected, the open-circuit detection function will oper-
ate and the converted temperature data will be set to 7FFF.
• The open-circuit detection function will be automatically cleared and nor-
mal input temperature conversion will begin automatically when the input
temperature returns to the convertible range.
Startup Operation
After power is turned ON, approximately 1 s is required for the first conversion
data to be stored in the input word. During that period, the data will be 7FFE.
Therefore, create a program as shown below, so that when operation begins
simultaneously with startup it will wait for valid conversion data.
Handling Unit Errors
• CP-series Expansion Unit/Expansion I/O Unit errors are output to bits 0 to
5 of word A436. The bits are allocated from A436.00 in order starting from
the Unit nearest the CPU Unit. CP1W-TS002 and CP1W-TS102 Temper-
ature Sensor Units are allocated two bits each. Use these flags in the pro-
gram when it is necessary to detect Expansion Unit/Expansion I/O Unit
errors.
• When an error occurs, the Temperature Sensor Unit data becomes 7FFF
hex (the same as for an open-circuit detection). With an open-circuit
detection, it is not reflected in word A436.
Input
Data conversion examples
Unit: 1
°
C
K or J
850
°
C
→
0352 hex
−
200
°
C
→
FF38 hex
Unit: 0.1
°
C
K, J, Pt100 or
JPt100
×
10
500.0
°
C
→
5000
→
1388 hex
−
20.0
°
C
→
−
200
→
FF38 hex
−
200.0
°
C
→
−
2000
→
F830 hex
(P_EQ)
1000.00
2
#7FFE
P_On
CMP(020)
Always ON
Temperature input data
output word
Initialization
Completed Flag
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......