Built-in Analog Input
Section 8-4
8-4
Built-in Analog Input
The CP1L-EL/EM CPU Units are equipped with 2 built-in analog inputs.
When a voltage of 0 to 10 V is applied to the built-in analog input terminal, the
voltage is converted from analog to digital and the PV in A642 and A643 can
be changed to any value within a range of 0 to 1000 (0000 to 03E8 hex).
Analog Input
Specifications
Analog Input Signal
Ranges
Analog input data is digitally converted according to the input signal range as
shown below.
Note
When the input exceeds the specified range, the A/D conversion data will be
fixed at either the lower limit or upper limit.
■
0 to 10 V
The 0 to 10 V range corresponds to the hexadecimal values 0000 to 03E8 (0
to 1000). The entire data range is 0000 to 044C (0 to 1100).
MAC Address:
01234567890A
BKUP
LNK/ACT
INH
ANALOG INPUT
V1+ V2+ COM
1
Built-in analog
input connector
Potentiometer, external
temperature sensor, etc.
0 to 10 V
00
NC
02
04
06
08
10
00
02
04
06
08
10
01
COM
03
05
07
09
11
01
03
05
07
09
11
00
01
02
03
04
06
00
01
03
04
06
COM
02
COM
05
07
COM
COM(V+)
05
07
MAC Address:
01234567890A
SYSMAC
CP1L
BKUP
ERR/ALM
LNK/ACT
POWER
RUN
INH
2
ANALOG INPUT
V1+ V2+ COM
EXP
1
Item
Specification
Number of inputs
2 inputs (2 words allocated in the AR Area)
Input signal range
Voltage input: 0 V to 10 V
Max. rated input
0 V to 15 V
External input impedance
100 k
Ω
min.
Resolution
1/1000 (full scale)
Overall accuracy
25°C: ±2.0% (full scale)
0 to 55°C: ±3.0% (full scale)
A/D conversion data
0000 to 03E8 hex
Averaging function
Not supported
Conversion time
Same as PLC cycle time
Isolation method
None
A642/A643 PV
Hexadecimal (Decimal)
10V
11V
03E8(1000)
044C(1100)
0000(0)
0V
Input voltage (V)
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......