343
Inverter Positioning
Section 7-3
A23
00 to 15 Inverter frequency
command value
(0.01-Hz increments,
unsigned)
Note
Set the Power
Supply Fre-
quency for
One Motor
Revolution per
Second, Num-
ber of
Encoder
Pulses for
One Motor
Revolution,
and Error
Counter Cycle
in the PLC
Setup before
using this
value.
0000 to FFFF hex
(0.00 to
655.35 Hz)
Cleared to zero at following times:
• When power to CPU Unit is turned ON
• At start of operation
• When an error counter error occurs
Updated at following times:
Cyclically according to error counter
cycle
These words con-
tain the automati-
cally calculated
frequency com-
mand value for the
inverter. (This value
is normally used.)
For example, if the
frequency setting
unit of the inverter
is 0.01 Hz, this
value can be used
as it in serial com-
munications with
the inverter. When
converting to an
analog output (0 to
5 V, 1 to 5 V, 0 to 10
V, 0 to 20 mA, or 4
to 20 mA), this
value can be used
to simplify the con-
version.
This value is used
when signed data
is not required, i.e.,
when using com-
munications or nor-
mal I/O to specify
the direction.
A24
00 to 15 Lower 4 digits of
present value of
signed output value
(output value =
present value of
error counter
×
error
counter cycle (s)
×
gain)
Note
The maxi-
mum and min-
imum output
values are
applied.
8000 0000 to 7FFF
FFFF hex
(
−
214,748,348 to
214,748,347)
Cleared to zero at following times:
• When power to CPU Unit is turned ON
• At start of operation
• When an error counter error occurs
Updated at following times:
• Cyclically according to error counter
cycle
This value can be
used when not
using automatic
frequency com-
mand calculations
and instead to con-
vert the output
value provided
here in the user
program for output
to the inverter.
This value is used
when signed data
is required, i.e.,
when outputting
the frequency com-
mand with an ana-
log output from
−
10
to 10 V.
A25
00 to 15 Upper 4 digits of
present value of
signed output value
(output value =
present value of
error counter
×
error
counter cycle (s)
×
gain)
Note
The maxi-
mum and min-
imum output
values are
applied.
Word
Bits
Function
Data range
Refresh timing
Application
examples
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......