115
I/O Area and I/O Allocations
Section 4-2
Example 2: Connecting Expansion I/O Units with Only Inputs or Only
Outputs
If Expansion I/O Units with only inputs or only outputs are connected, the
input or output word not used by an Expansion I/O Unit is allocated to the next
Unit that requires it.
4-2-4
I/O Word Allocations to Expansion Units
m:
Indicates the next input word after the input word allocated to the
Expansion Unit, Expansion I/O Unit, or CPU Unit to the left of the cur-
rent Unit.
n:
Indicates the next output word after the output word allocated to the
Expansion Unit, Expansion I/O Unit, or CPU Unit to the left of the cur-
rent Unit.
Unit
Input words
Output words
Analog I/O Units
CP1W-MAD11
2 words CIO m to CIO m+1 1 word
CIO n
CP1W-MAD42
4 words CIO m to CIO m+3
2 words CIO n to CIO n+1
CP1W-MAD44
4 words CIO m to CIO m+3
4 words CIO n to CIO n+3
Analog Input Units
CP1W-AD041
CP1W-AD042
4 words CIO m to CIO m+3
2 words CIO n to CIO n+1
Analog Output Units
CP1W-DA021
None
---
2 words CIO n to CIO n+1
CP1W-DA041
CP1W-DA042
None
---
4 words CIO n to CIO n+3
Temperature Sensor Units
CP1W-TS001
2 words CIO m to CIO m+1
None
---
CP1W-TS002
4 words CIO m to CIO m+3
None
---
CP1W-TS003
4 words CIO m to CIO m+3
None
---
CP1W-TS004
2 words CIO m to CIO m+1
1 word
CIO n
CP1W-TS101
2 words CIO m to CIO m+1
None
---
CP1W-TS102
4 words CIO m to CIO m+3
None
---
CompoBus/S I/O Link
Units
CP1W-SRT21
1 word
CIO m
1 word
CIO n
104.00
104.07
Bit
15 14 13 12
11 10 09 08 07 06
05 04 03 02 01 00
CIO 0
CIO 1
CIO 2
CIO 3
CIO 100
CIO 101
CIO 102
CIO 103
CIO 104
Do not use.
Can be used as work bits.
18 input points
12 output points
CPU Unit
(30 I/O points)
8 input points
CIO 0.00 to CIO 0.11
CIO 1.00 to CIO 1.05
CIO 100.00 to CIO 100.07
CIO 101.00 to CIO 101.03
CIO 2.00 to CIO 2.07
CIO 102.00 to CIO 102.07
CIO 103.00 to CIO 103.07
No outputs
16 output points
No inputs
12 input points
8 output points
CIO 3.00 to CIO 3.11
CIO 104.00 to CIO 104.07
First Expansion I/O Unit:
Unit with 8 inputs
Second Expansion I/O Unit:
Unit with 16 outputs
Third Expansion I/O Unit:
Unit with 20 I/O
CPU Unit with 30 I/O points
First Expansion I/O Unit: Unit with 8 inputs
Third Expansion I/O Unit: Unit with 20 I/O
CPU Unit with 30 I/O
points
Second Expansion I/O Unit:
Unit with 16 outputs
Third Expansion I/O Unit: Unit with 20 I/O
Input bits
Input bits
Output bits
Output bits
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......