Pulse Outputs
Section 7-2
If origin compensation is not being applied, the Positioning Completed Signal
is checked after the Error Counter Reset Output. If origin compensation is
being applied, the Positioning Completed Signal is checked after the compen-
sation operation is completed.
Origin Search Operation
Setting
Select either of the following two reverse modes for the origin search opera-
tion pattern.
Origin Detection Method
The origin detection method depends on the Origin Proximity Input Signal set-
tings. Select one of the following three methods in each port’s parameters.
Origin Detection Method 0: Origin Proximity Input Signal Reversal
Required
1
1
0
0
Pulse output
Error Counter
Reset Output
Positioning
Completed
Signal
Stop
Time
Setting
Description
0: Reversal mode 1
When the limit input signal is received in the origin search
direction, reverse and continue operation.
1: Reversal mode 2
When the limit input signal is received in the origin search
direction, generate an error and stop operation.
Setting
Description
0: Origin Proximity Input Signal
reversal required.
Reads the first Origin Input Signal after the Ori-
gin Proximity Input Signal goes
OFF
→
ON
→
OFF.
1: Origin Proximity Input Signal
reversal not required.
Reads the first Origin Input Signal after the Ori-
gin Proximity Input Signal goes OFF
→
ON.
2: Origin Proximity Input Signal not
used.
Just read the Origin Input Signal without using
the Origin Proximity Input Signal.
1
1
0
0
CCW
CW
Origin Proximity
Input Signal
Origin Input
Signal
Pulse output
Deceleration starts when
Origin Proximity Input
Signal goes OFF
→
ON.
After the Origin Proximity Input Signal has gone
from OFF
→
ON
→
OFF, the motor is stopped
when the Origin Input Signal goes OFF
→
ON.
Initial
speed
Acceleration
High speed for
origin search
Deceler-
ation
Proximity speed for origin search
Start when
ORG(889) is
executed.
Stop
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......