259
Pulse Outputs
Section 7-2
■
Limit Input Signal Setting
Specify in the following PLC Setup whether to use the CW/CCW limit input
signals only for origin searches or for all pulse output functions. These set-
tings affect all pulse outputs.
(This setting is called the Limited Input Signal Operation setting.)
■
Pulse Output 0 Undefined Origin Setting
■
Acceleration/Deceleration Curve Settings
Note
The acceleration/deceleration curve setting applies to all pulse outputs, not
just to origin searches. Refer to S-curve Acceleration/Deceleration on
page 253 for details.
Origin Search Parameters
The various origin search parameters are set in the PLC Setup.
Name
Settings
Time when
read
Operating mode
Operating mode 0, 1, or 2
Start of
operation
Origin search operation
setting
0: Reversal mode 1
1: Reversal mode 2
Start of
operation
Origin detection method
0: Read the Origin Input Signal after the
Origin Proximity Input Signal goes
from OFF
→
ON
→
OFF.
1: Read the Origin Input Signal after the
Origin Proximity Input Signal goes
from OFF
→
ON.
2: Just read the Origin Input Signal with-
out using the Origin Proximity Input
Signal.
Start of
operation
Origin search direction
0: CW direction
1: CCW direction
Start of
operation
Origin
search
speed
(See
note.)
Origin search/
return initial
speed
00000000 to 000186A0 hex
(0 Hz to 100 kHz)
Start of
operation
Origin search
high speed
00000001 to 000186A0 hex
(1 Hz to 100 kHz)
Start of
operation
Origin search
proximity speed
Same as above.
Start of
operation
Origin search
acceleration rate
0001 to FFFF hex (1 to 65,535 Hz/4 ms)
Start of
operation
Origin search
deceleration rate
0001 to FFFF hex (1 to 65,535 Hz/4 ms)
Start of
operation
Origin compensation
8000 0000 to 7FFF FFFF hex
(
−
2147483648 to 2147483647)
Start of
operation
I/O settings
Limit Input Signal type
0: Normally closed (NC)
1: Normally open (NO)
Start of
operation
Origin Proximity Input Signal type
0: Normally closed (NC)
1: Normally open (NO)
Start of
operation
Origin Input Signal type
0: Normally closed (NC)
1: Normally open (NO)
When power
is turned ON
Positioning monitor time
0000 to 270F hex
(0 to 9,999 ms)
Start of
operation
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......