480
Analog Output Units
Section 9-3
■
Set Data
• The Analog Output Unit will not start converting analog output values until
the set data has been written.
• Before the range code is written, 0 V or 0 mA will be output in the 0 to 10
V,
−
10 to +10 V, and 0 to 20 mA ranges, and 1 V or 4 mA will be output in
the 1 to 5 V and 4 to 20 mA ranges.
• Once the range code has been set, it is not possible to be changed while
power is being supplied to the CPU Unit. To change the range code, turn
the CPU Unit OFF then ON again.
Writing Analog Output
Conversion Values
The ladder program can be used to write conversion data to the output words.
The output word starts from “n+1” where “n” is the last output word allocated
to the CPU Unit, or previous Expansion Unit or Expansion I/O Unit.
Startup Operation
After power is turned ON, it will require two cycle times plus approximately
50 ms before the first conversion data is output.
The following table shows the output status after the initial processing is com-
pleted.
Therefore, create a program as shown below, so that when operation begins
simultaneously with startup it will wait for valid set data.
0
1
Range code
Analog output range
−
10 to 10 V
0 to 10 V
1 to 5 V
0 to 20 mA
4 to 20 mA
000
001
010
011
100
Output use
No
Yes
Output type
Voltage output
Current output
Output range
0 to 10 V,
−
10 to +10 V
1 to 5 V
0 to 20 mA
4 to 20 mA
Before range
code is written
0 V
0 mA
After range
code is written
0 V
1 V
0 mA
4 mA
MOV(021)
D100
102
P_On
Always ON Flag
T0005
0005
TIM
#0002
TIM0005 is started when the power is
turned ON. After 0.2 s (200 ms) elapses,
the TIM0005 contact turns ON, and the
data stored in D100 will be moved to
102 as the conversion data for analog
output 1.
Содержание CP1L-EL20DR-D
Страница 3: ...CP1L EL20D CP1L EM30D CP1L EM40D CP1L EL EM CPU Unit Operation Manual Produced July 2017...
Страница 4: ...iv...
Страница 10: ...x...
Страница 22: ...xxii...
Страница 34: ...xxxiv Software Licenses and Copyrights 7...
Страница 178: ...144 Connecting the CX Programmer Section 5 1 Click the Connect button to connect and then connection online is completed...
Страница 192: ...158 Trial Operation and Debugging Section 5 3...
Страница 250: ...216 Automatic Clock Adjustment and Specifying Servers by Host Name Section 6 7...
Страница 666: ...632 Trouble Shooting Section 11 7...
Страница 696: ...662 Standard Models Appendix A...
Страница 805: ...771 Connections to Serial Communications Option Boards Appendix F Connecting to Unit...
Страница 806: ...772 Connections to Serial Communications Option Boards Appendix F...
Страница 836: ...802 PLC Setup Appendix G...
Страница 838: ...804 TCP Status Transitions Appendix H...
Страница 840: ...806 Ethernet Network Parameters Appendix I...
Страница 842: ...808 Buffer Configuration CP1L EL EM Appendix J...
Страница 844: ...810 Ethernet Specifications Appendix K...
Страница 851: ...Index 817 work words 118 write protection 447...
Страница 852: ...818 Index...
Страница 854: ...820 Revision History...
Страница 855: ......