3. Fieldbus Integration With Experion System
3.8. Block Instantiation Support
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
95
July 2010
Honeywell
If you want
to . . .
Then,
Notes and References
ATTENTION
Be sure you load a device from
Project
before you load a Control Module
that contains instantiable blocks. If you load a Control Module that contains
instantiable block(s) before the associated device in
Project
is loaded and its
blocks instantiated, the Control Module load will fail.
De-
instantiate
(delete) an
instantiated
block from
Project tab.
u) Open device icon hierarchy in
Project tab.
v) Right-click applicable instantiated
block icon in hierarchy and select
delete from the shortcut menu.
w) Click Continue button to initiate
action and track progress in
Delete dialog.
x) Upon successful deletion the
instantiated block icon is removed
form the device hierarchy.
You cannot delete an
instantiated block that is
contained in a Control
Module unless you un-
assign or delete the block
from the CM first.
Also, you cannot delete an
Instantiable block from
Project, if it is loaded and
viewable in the Monitor tab.
De-
instantiate
(delete) an
instantiated
block from
physical
device
y) You cannot delete an instantiated
block directly from a physical
device.
z) You must first delete the CM from
Monitor, unassign or delete the
instantiated block from CM in
Project tab, and then delete the
block as noted in the row above.
aa) Load device from Project to re-
synchronize contents with
physical device.
bb) Load reconfigured CM.
cc) Right-click device icon and select
Upload from the shortcut menu.
Click Continue to load device data
into the Monitor database.
You must re-load Project
device to re-synchronize
contents with physical device
after any control strategy
changes or physical device
maintenance that may alter
contents in either device.
Deleting a block from
Monitor tab, does not de-
instantiate a block in a
device. Only a load of a
device will achieve this.