4. Installation
4.3. Installing Fieldbus RTP TC-FFRU01/TC-FFRP02 or RRTP TC-FFSU01/TC-FFSP02
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
113
July 2010
Honeywell
Step Action
1
Be sure the enclosure is connected to a protective earth ground using #8
AWG solid copper wire. There should be metal to metal contact between the
grounding bus bar and the enclosure as well as the DIN rails
2
RTP model TC-FFRU01 or (RRTP model TC-FFSU01)
: Observing polarity,
connect the positive (+) lead for the fieldbus H1 link 1 cable to terminal J2-1
(J5-1) or J2-2 (J5-2) FB+ and the negative (-) lead to J2-4 (J5-4) or J2-5 (J5-
5) FB-. Connect the cable shield to terminal J2-6 (J5-6) SHIELD or to the bus
bar in the enclosure. See the following wiring schematic for TC-FFRU01 or
TC-FFSU01 for reference.
RTP model TC-FFRP02 or RRTP Model TC-FFSP02
: Observing polarity,
connect the positive (+) lead for the fieldbus H1 link 1 cable to terminal 2 FB+
and the negative (-) lead to 1 FB- on the GI/IS power supply at location J3.
Connect the cable shield to the bus bar in the enclosure. See the following
wiring schematic for TC-FFRP02 for reference.
3
RTP model TC-FFRU01 or RRTP model TC-FFSU01
: Observing polarity,
connect the positive (+) lead for the fieldbus H1 link 2 cable to terminal J7-1
or J7-2 FB+ and the negative (-) lead to J7-4 or J7-5 FB-. Connect the cable
shield to terminal J7-6 SHIELD or to the bus bar in the enclosure.
RTP model TC-FFRP02 or (RRTP model TC-FFSP02)
: Observing polarity,
connect the positive (+) lead for the fieldbus H1 link 2 cable to terminal 2 FB+
and the negative (-) lead to 1 FB- on the GI/IS power supply at location J8
(J4). Connect the cable shield to the bus bar in the enclosure.
4
Connect the plug on the RTP cable from the CIOM-A FIM to the RTP
Cable connector J1 on the
RTP model TC-FFRU01 or TC-FFRP02
for
non-redundant application or
RRTP model TC-FFSU01 or TC-FFSP02
for redundant application.
For redundant CIOM-A FIM applications, connect the plug on the RTP
cable from the matching CIOM-A FIM in the Redundant Chassis Pair to
the RTP Cable connector J2 on the
RRTP model TC-FFSU01 or TC-
FFSP02
.
5
RTP model TC-FFRP02
: Observing polarity, connect the positive (+) lead for
the 24 Vdc power supply cable to terminal J10-2 V+ and the negative (-) lead
to J10-1 V-.
RRTP model TC-FFSP02
: Observing polarity, connect the positive (+) lead
for the 24 Vdc power supply cable for link 1 to terminal J9-1 + and the
negative (-) lead to J9-2 -. Connect positive lead for the 24 Vdc power supply
for link 2 to terminal J10-1 + and the negative (-) lead to J10-2 -.
6
Go to the next section
Configuration
to include the CIOM-A FIM and fieldbus
devices in the configured control strategy.