8. Maintenance, Checkout, and Calibration
8.8. Preparing Fieldbus Device for a Move or Software Migration
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
343
July 2010
Honeywell
Step Action
Result
19
Click the
button and select Simulate
Disabled.
Opens Change Online Value
confirmation dialog.
20
Click Yes.
Disables the simulate function and
returns the fieldbus device to normal
operation.
21
Click the OK button.
Closes the Block Parameter form.
22
This completes the simulate function
example procedure.
8.8 Preparing Fieldbus Device for a Move or Software
Migration
During migration to R400, EDDL constructs are ignored. Therefore, you need to
manually import the latest DD files after migrating to R400. For more information on
importing of DD files, see Creating a Fieldbus device type from vendor DD.
The process of importing the DD files enables interpreting the EDDL constructs along
with Conditionals.
ATTENTION
The DD files must have the latest EDDL constructs to make use of the
additional features, which are supported by the Experion host.
There is no limitation on the number of conditionals for the Experion host
to support.
Experion host supports version 1.9 of Device Capability File (.CCF) files.
Use the following procedure to prepare a device before migrating the system to a new
software release or moving the device to another Link. All the illustrations used in the
procedure are for example purposes only.