8. Maintenance, Checkout, and Calibration
8.3. Replacing Device Template with a Different One
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
327
July 2010
Honeywell
Step Action
16
If error or warning messages appear in the Unlike Template Replacement
Results list box, click the
View Replacement Log
button to call up the
FF_UTR_Log to review replacement results.
If the message includes an error code reference, refer to the
Control Builder
Error Code Reference
document for more information. For example, if the
message includes a reference like, [EXPKS_E_CL_INVLCYCST
(4L.101.10110)], the last five digits (10110) represent the error code.
17
Click the
DONE
button to close the wizard. If applicable, correct any errors
and repeat the procedure.
18
The completes the procedure, go to the next section.